IEC Rated Motor Data.



IEC Rated Motor Data.

.

Motor KWMotor Power Factor Motor Efficiency (%) Rated Current at 220VAC Rated Current at 380VAC Rated Current at 415VAC Rated Current at 500VAC
0.25 0.7 62 1.4 0.8 0.7 0.6
0.37 0.72 64 2.1 1.2 1.2 0.9
0.55 0.75 69 2.7 1.6 1.6 1.2
0.75 0.8 74 3.4 2 1.8 1.5
1.1 0.83 77 4.4 2.6 2.6 2
1.5 0.83 78 6 3.5 3.5 2.6
2.2 0.83 81 8.7 5 5 3.7
3 0.84 81 11.5 6.6 6.2 5
4 0.84 82 14.7 8.5 7.5 6.4
5.5 0.85 83 19.8 11.5 11 9
7.5 0.86 85 26.5 15.5 14 11.5
11 0.86 87 39 22.5 21 17
15 0.86 87 52 30 28 22.5
18.5 0.86 88 64 36 35 28
22 0.87 89 75 43 40 32
30 0.87 90 100 58 55 43
37 0.87 90 124 72 66 54
45 0.88 91 147 85 80 64
55 0.88 91 180 104 100 78
75 0.88 91 246 142 135 106
90 0.88 92 292 169 165 127
110 0.88 92 357 204 200 154
132 0.88 92 423 243 230 182
130 0.88 93 500 292 275 220
200 0.88 93 620 368 324 283
250 0.88 93 775 465 425 355
315 0.88 93 977 580 530 444
400 0.89 96 1240 720 672 534
500 0.89 96 1550 900 840 667


Notes:
#1. When Manufacturer data is different from the above information, default to manufacturer data.
#2. These values are for educational purposes only.
Due to the wide range of circuit applications, the author assumes no responsibility for the application of these values.


Select here for Tom's HOME page